Model / PN |
ORVALDI V1000 (L)on-line 2U LCD / VGA1K(L)
|
ORVALDI V2000 (L) on-line 2U LCD / VGA2K(L) |
ORVALDI V3000 (L) on-line 2U LCD / VGA3K(L) |
ORVALDI V6000 (L) on-line 3U LCD / VGA6K(L) |
ORVALDI V10000 (L) on-line 3U LCD / VGA10K(L) |
Phase |
Single phase with ground |
Capacity |
1000 VA / 800 W |
2000 VA / 1600 W |
3000 VA / 2400 W |
6000 VA / 4800 W |
10000 VA / 8000 VA |
INPUT |
Frequency Range |
45Hz ~ 55 Hz or 56Hz ~ 65 Hz |
46~54 Hz or 56~64 Hz |
Power Factor |
≧ 0.99 |
≧ 0.99 @ 100%load |
Voltage Range |
Low Line Transfer |
80 VAC/70 VAC/60 VAC/50 VAC ± 5% or 160 VAC/140 VAC/120 VAC/110 VAC ± 5% (based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
176 VAC ± 3% @ 100% load ; 110 VAC ± 3% @ 50% load |
Low Line Comeback |
85 VAC / 75VAC / 65 VAC / 55VAC ± 5 % or 170 VAC /150 VAC/ 130 VAC /120 VAC± 5 % |
186 VAC ± 3% @ 100% load ; 120 VAC ± 3% @ 50% load |
High Line Transfer |
150 VAC ± 5 % or 300 VAC ± 5 % |
300 VAC ± 3% |
High Line Comeback |
145 VAC ± 5 % or 290 VAC ± 5 % |
290 VAC ± 3% |
|
OUTPUT |
Output Voltage |
110/115/120/127 VAC or 208/220/230/240 VAC |
208/220/230/240 VAC |
AC Voltage Regulation (Batt. Mode) |
± 1% |
± 1% |
Frequency Range (Synchronized Range) |
48 ~ 52 Hz or 58 ~ 62 Hz |
46~54 Hz or 56~64 Hz |
Frequency Range (Batt. Mode) |
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz |
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio |
3:1 |
3:1 |
Harmonic Distortion |
≦ 2 % THD (Linear Load), 8% max. (Batt. mode before shut down) |
≦ 3 % THD (Linear Load) ; ≦ 6 % THD (Non-linear Load) |
Waveform (Batt. Mode) |
Pure Sinewave |
Transfer Time |
AC Mode to Batt. Mode |
Zero |
Inverter to Bypass |
4 ms (Typical) |
Zero |
|
EFFICIENCY |
AC Mode |
86% |
88% |
89% |
Battery Mode |
83% |
85% |
88% |
BATTERY |
Standard Model |
Battery Type |
12 V / 9 Ah |
12 V / 7 Ah |
|
12 V / 9 Ah |
12 V / 7Ah |
12 V / 9Ah |
12 V / 7 Ah |
12 V / 9 Ah |
Numbers |
2 |
3* |
|
4 |
6* |
6 |
20 |
20 |
Charging Voltage |
27.4 VDC ± 1% |
41.1 VDC ± 1% |
|
54.8 VDC ± 1% |
82.1 VDC ±1% |
82.1 VDC ±1% |
273 VDC ±1% |
Charging Current (max.) |
1.0 A |
2.0 A |
Typical Recharge Time |
4 hours recover to 90% capacity |
3 hours recover to 90% capacity |
4 hours recover to 90% capacity |
|
Long-run Model |
Battery Type |
Depending on the capacity of external batteries |
Depending on applications |
Numbers |
Depending on the capacity of external batteries |
18-20 |
Charging Current (max.) |
8.0 A |
2.0 A |
Charging Voltage |
27.4 VDC ± 1% |
41. 1 VDC ± 1% |
|
54.8 VDC ± 1% |
82.1 VDC ±1% |
82.1 VDC ±1% |
273.0 VDC ±1% |
|
INDICATORS |
LCD Display |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
ALARM |
Battery Mode |
Sounding every 4 seconds |
Low Battery |
Sounding every second |
Overload |
Sounding twice every second |
Fault |
Continuously sounding |
PHYSICAL |
Standard Model |
Dimension, D x W x H (mm) |
380 x 438 x 88 [2U] |
480 x 438 x 88 [2U] |
|
480 x 438 x 88 [2U] |
600 x 438 x 88 [2U] |
600 x 438 x 88 [2U] |
UPS Unit : 580 x 438 x133 [3U] ; Battery Pack : 580 x 438 x 133 [3U] |
UPS Unit: 668 x 438 x 133 [3U] ; Battery Pack : 580 x438 x 133 [3U] |
Net Weight (kgs) |
13.2 |
18.4 |
|
20.6 |
25.7 |
29 |
UPS Unit : 17 ; Battery Pack : 57 |
UPS Unit : 20 ; Battery Pack : 63 |
|
Long-run Model |
Dimension, D x W x H (mm) |
380 x 438 x 88 [2U] |
480 x 438 x 88 [2U] |
|
480 x 438 x 88 [2U] |
600 x 438 x 88 [2U] |
600 x 438 x 88 [2U] |
580 x 438 x 133 [3U] |
668 x 438 x 133 [3U] |
Net Weight (kgs) |
9.1 |
11.3 |
|
11.3 |
14.6 |
14.8 |
17 |
20 |
|
ENVIRONMENT |
Humidity |
20-90 % RH @ 0- 40°C (non-condensing) |
Noise Level |
Less than 50dB @ 1 Meter |
Less than 55dBA @ 1 Meter |
Less than 58dBA @ 1 Meter |
MANAGEMENT |
Optional SNMP |
Power management from SNMP manager and web browser |
Smart RS-232/USB |
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC |